基于内模控制的主动悬挂电液伺服作动器位置控制研究
作者:
作者单位:

作者简介:

通讯作者:

中图分类号:

基金项目:

国家重点研发计划项目(2016YFC0802902)


Internal Model Control in Position Control of Active Suspension Electrohydraulic Servo Actuator
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    针对负载质量和负载力等参数不确定的主动悬挂电液伺服作动器位置控制系统,采用内模控制方法对其进行位置控制。根据系统特性建立了电液伺服作动器位置控制系统线性化数学模型,并基于此模型设计了内模控制器。为验证内模控制器的控制效果,进行了与PID控制的对比仿真分析和台架试验。以阶跃信号为输入信号进行了仿真分析,仿真结果表明,系统在内模控制下的单位阶跃响应快速、平稳、无超调,动态特性优于PID控制,且当系统受到外部干扰时,内模控制比PID控制能更快速、平稳地恢复至稳态值。台架试验包括改变正弦输入信号频率和改变负载质量两种试验方案。结果表明,当正弦输入信号频率由0.1Hz增加至2Hz时,基于PID控制的系统跟踪性能明显恶化,而基于内模控制的系统跟踪性能并无明显变化;当负载质量发生变化时,基于内模控制的系统跟踪误差变化幅度明显小于PID控制。基于内模控制的电液伺服作动器位置控制系统的跟踪响应性能优于PID控制,满足主动悬挂系统的使用要求。

    Abstract:

    Aiming at the position control system of active suspension electrohydraulic servo actuator with uncertain load mass and load force, the internal model control method was used to control the position of the actuator. Firstly, according to the characteristics of the system, the linear mathematical model of the electrohydraulic servo actuator position control system was established, and then the internal model controller was designed based on the model. In order to verify the control effect of internal model controller, the simulation analysis and bench test were compared with PID controller. The step signal was used as the input signal for simulation analysis. The simulation results showed that the unit step response of the system under internal model control was fast, stable, no overshoot, and its dynamic characteristics were better than that of PID control. When the system was disturbed by external interference, it can return to the steady value more quickly and stably than PID control. The bench test included changing the frequency of sinusoidal input signal and changing the load quality. There were three kinds of experimental schemes. The experimental results showed that when the frequency of sinusoidal input signal was increased from 0.1Hz to 2Hz, the tracking performance of the system based on internal model control had no obvious change, while the tracking performance of the system based on PID control was obviously deteriorated when the sinusoidal input signal frequency was 2Hz; the test results of changing load quality showed that when the load quality was changed, the system based on internal model control had no obvious change. The variation range of tracking error was obviously smaller than that of PID control. The tracking response performance of electrohydraulic servo actuator position control system based on internal model control was better than that of PID control, and can meet the requirements of active suspension system.

    参考文献
    相似文献
    引证文献
引用本文

郭庆贺,赵丁选,赵小龙,李振兴,武理哲,师小波.基于内模控制的主动悬挂电液伺服作动器位置控制研究[J].农业机械学报,2020,51(12):394-404. GUO Qinghe, ZHAO Dingxuan, ZHAO Xiaolong, LI Zhenxing, WU Lizhe, SHI Xiaobo. Internal Model Control in Position Control of Active Suspension Electrohydraulic Servo Actuator[J]. Transactions of the Chinese Society for Agricultural Machinery,2020,51(12):394-404.

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2020-08-06
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2020-12-10
  • 出版日期: 2020-12-10