5.90和3.56。The Exergy analytical method was adopted to analyze the performance of groundwater source heat pump (GSHP) system by applying Exergy destruction Edest and Exergy efficiency ε. Related Exergy analytical models have been put forward according to the cooling experiment carried out in an office building and a Chinese solar greenhouse in the summertime of 2007. Analytical results showed that the evaporator has a higher Exergy efficiency than other parts of the system, which reached 95%. However, the Exergy efficiency of condenser and total GSHP system was not very satisfying. Meanwhile, the coefficient of performance of GSHP unit and total system has reached 5.90 and 3.56 respectively.
参考文献
相似文献
引证文献
引用本文
柴立龙,马承伟,袁小艳,张义,余飞.基于Exergy研究的地源热泵降温系统性能分析[J].农业机械学报,2009,40(2):146-150. Performance Analysis on Ground Source Heat Pump Cooling System Based on Exergy Research[J]. Transactions of the Chinese Society for Agricultural Machinery,2009,40(2):146-150.